LPFI - Load Break Switching & Fault Interrupting

G&W Electric model LPFI padmount switches include load break and fault interrupting capability. The fault interrupters provide electronically controlled, resettable over current protection in a totally sealed, dead front device. The switches are designed for use on 3-phase systems with voltages up to 27kV, 630A load break, and continuous current, and 12.5kA symmetrical fault interrupting ratings. They feature compact footprints due to their front access construction.

The switches are designed to IEEE C37.72, C37.74, and C37.60 for load break and fault interrupting capability. Padmount enclosures are designed and tested to IEEE C57.12.28 and C57.12.29.

Configure Your Product Email your specs

Features and Benefits

Configurations Chart for LPFI
# of WaysOne-line Diagram (Horizontal)Voltage Class (kV)Catalog Number
Approximate
Width* in. (mm)Wt. w/SF6 lbs (kg)
5F
15LPFI21-376-12-5F43.5 (1111)1475 (670)
25LPFI21-386-12-5F
6F
15LPFI32-376-12-6F56.3 (1429)1775 (807)
25LPFI32-386-12-6F
7F
15LPFI31-376-12-7F55.7 (1415)2100 (995)
25LPFI31-386-12-7F
9F
15LPFI42-376-12-9F68.3 (1734)2100 (995)
25LPFI42-386-12-9F
11F
15LPFI43-376-12-11F68.8 (1746)2075 (943)
25LPFI43-386-12-11F
12F
15LPFI41-376-12-12F67.8 (1721)2150 (977)
25LPFI41-386-12-12F
43F
15LPFI43-376-12-43F-BT80.2 (2037)2300 (1045)
25LPFI43-386-12-43F-BT
51F
15LPFI51-376-12-51F79.7 (2025)2600 (1182)
25LPFI51-386-12-51F
52F
15LPFI52-376-12-52F80.3 (2038)2525 (1148)
25LPFI52-386-12-52F
53F
15LPFI53-376-12-53F80.8 (2051)2450 (1114)
25LPFI53-386-12-53F
54F
15LPFI54-376-12-54F81.3 (2064)2400 (1091)
25LPFI54-386-12-54F
62F
15LPFI62-376-12-62F92.3 (2343)2800 (1273)
25LPFI62-386-12-62F
63F
15LPFI63-376-12-63F92.8 (2356)2750 (1250)
25LPFI63-386-12-63F
64F
15LPFI64-376-12-64F93.3 (2369)2700 (1227)
25LPFI64-386-12-64F
65F
15LPFI65-376-12-65F93.7 (2381)2650 (1205)
25LPFI65-386-12-65F
72F
15LPFI72-376-12-72F104.3 (2648)3100 (1409)
25LPFI72-386-12-72F
Approximate Height: 61" (1549mm), Approximate Depth = 54" (1372mm)
Configuration Chart for VLPFI
ModelOne-line Diagram (Horizontal)Voltage Class (kV)Catalog Number
Approximate
Width* in. (mm)Wt. w/SF6 lbs (kg)
5F
15VLPFI21-376-12-5F45 (1149)1025 (466)
25VLPFI21-386-12-5F
6F
15VLPFI32-376-12-6F57.5 (1467)1250 (568)
25VLPFI32-386-12-6F
7F
15VLPFI31-376-12-7F57 (1454)1300 (591)
25VLPFI31-386-12-7F
9F
15VLPFI42-376-12-9F69.5 (1772)1350 (614)
25VLPFI42-386-12-9F
11F
15VLPFI43-376-12-11F70 (1784)1325 (602)
25VLPFI43-386-12-11F
12F
15VLPFI41-376-12-12F69 (1759)1400 (636)
25VLPFI41-386-12-12F#rowspan##rowspan#
43F
15VLPFI43-376-12-43F89 (2261)1800 (818)
25VLPFI43-386-12-43F
51F
15VLPFI51-376-12-51F81 (2064)1950 (886)
25VLPFI51-386-12-51F
52F
15VLPFI52-376-12-52F81.5 (2064)1875 (852)
25VLPFI52-386-12-52F
53F
15VLPFI53-376-12-53F82 (2089)1800 (818)
25VLPFI53-386-12-53F
54F
15VLPFI54-376-12-54F82.5 (2102)1750 (795)
25VLPFI54-386-12-54F
62F
15VLPFI62-376-12-62F93.5 (2381)2000 (909)
25VLPFI62-386-12-62F
63F
15VLPFI63-376-12-63F94 (2394)1950 (886)
25VLPFI63-386-12-63F
64F
15VLPFI64-376-12-64F94.5 (2407)1900 (864)
25VLPFI64-386-12-64F
65F
15VLPFI65-376-12-65F95 (2419)1850 (841)
25VLPFI65-386-12-65F
72F
15VLPFI72-376-12-72F105.5 (2680)2000 (909)
25VLPFI72-386-12-72F
Approximate Height: 31" (787mm), Approximate Depth = 28" (711mm)
Ratings Chart for LPFI and VLPFI
Voltage class15kV25kV
Maximum design voltage15.5kV27kV
Impulse level (BIL)110kV125kV
One minute withstand35AC kV60AC kV
One minute withstand, production test rating34AC kV40AC kV
15 minute withstand53DC kV78DC kV
Continuous and load break current630 Amps630 Amps
Load Break Switch Momentary current40kA asym40kA asym
Load Break Switch Fault close current, (3 times)40kA asym40kA asym
Load Break Switch One second current25kA asym25kA asym
Fault Interrupter Symmetrical interrupting rating12.5kA12.5kA
Load Break Switch Open gap withstand200kV200kV
Load Break Switch 10 operation overload interrupting capability3000 Amps3000 Amps
Operations load interrupting endurance at 600A for Load Break Switch12001200
Mechanical endurance, operations20002000
IEEE C37.60 Fault Interrupting Duty
Total number of fault interruptions: 116
Percent of Maximum Interrupting RatingApprox. Interrupting Current, Amps
15 – 20%2,000
45 – 55%6,000
90 – 100%12,500

For Accessories and additional options see full catalog

Product Literature

Gas Insulated Switchgear – Padmount

Download

Gas Insulated Switchgear – Vault

Download

Vacuum Interrupter (VI Control)

Download

Gas Insulated Switching Solutions Brochure

Download
Case Studies

University FLISR Solution

Download

University Network Upgrade with Automation

Download

Reducing System Outages & Increase Reliability

Download

Airport Feeder Restoration

Download

Industrial Manufacturing Feeder Restoration

Download
Application Guides

Submersible Switchgear Applications

Download

Closed Loop Automation for Ship Locks

Download
Specifications

LPFI (automatic transfer) Specification

Download

LPFI (manually operated) Specification

Download

VLPFI Specification

Download