
Figure
1: Primary-Selective Configuration |
Primary-Selective
Configuration:
The most common auto
transfer system is a primary-selective, or common bus configuration
(see Figure 1). In this scenario, actuators and voltage sensors
(analog or digital type) are installed on the switches for
incoming source 1 and incoming source 2. One of the source
switches is normally closed (feeding the load), and one is
normally open (waiting as a standby or alternate source).
If the load way(s) are load break only (non-fault-interrupting
devices), optional faulted circuit indicators may be added
for downstream fault indication. All of these devices are
wired into the ATC control.
Preferred/Alternate Setting:
Either
of the incoming sources may be programmed as the preferred,
or primary source. In this setting mode, the preferred source
switch is normally closed, and the alternate source switch
is normally open. Voltage sensors interface with the ATC to
indicate the source voltages as either "live" or
"dead." If the preferred source voltage is dead,
the ATC will initiate a transfer to the alternate source,
providing that its' voltage is live. When the preferred source
voltage is live again, the ATC will initiate a transfer back
to the preferred source. These transfers will occur in "open-before-close"
or "close-before-open" user-programmable operation
sequences.
Non-Preferred Setting:
Certain ATC applications
do not require a preferred source. In this setting mode, the
ATC will only initiate a transfer if the source that is feeding
the load is dead. There is no return transfer when a non-preferred
mode is selected.
Bus-Tie Configuration (Figure 2)
Bus-tie systems split the load into two sections. One of the
load sections is fed by normally-closed incoming source 1
and the other load section is fed by normally-closed incoming
source 2. A normally-open switch (bus-tie switch) separates
the two sections. Actuators are installed on switches for
source, source 2, and the bus-tie. Voltage sensors (analog
or digital) are installed on the two incoming source switch
ways. If the load ways are load break only, optional faulted
circuit indicators may be added for down-stream fault indication.
All of these devices are wired into the automatic transfer
control (ATC). In bus-tie ATC systems, if either source
is dead (and the remaining source is live), the control will
initiate a transfer by opening the dead source switch and
closing the bus-tie switch. Once the source is live again,
the control will transfer back to its normal state by opening
the bus-tie switch and closing the source switch. These transfers
will occur in "open-before-close" or "close-before-open"
user-programmable operation sequences.
Generator Source Configuration
In some ATC applications, rather than two utility sources,
a generator is used as the alternate source. In this application,
once the utility source is dead, the control will automatically
issue a start command to the generator. It will then monitor
the incoming voltage from the generator, initiating a transfer
to the generator source only after it measures a live source.
When the utility source is live again, the ATC control will
initiate a return transfer operation. Simultaneously, it will
issue a stop, or cool-down command to the generator.
Custom ATC Configurations
While a majority of the auto transfer applications will fall
within the previous three categories, there is a need for
specialized ATC configurations. G&W provides custom ATC
schemes that include integral SCADA systems and distributed
source applications.
|