G & W Electric
ISO 9001: 2000 and 14001 Certified
More Information
Specifications
Configurations
Motor Actuators
ATC 101 Panel
ATC 201 Panel
Application Guide (AG7)
Literature
     

ATC Typical Specifications

GENERAL


The automatic source transfer control (ATC) is designed to work with G&W SF6 and solid dielectric switchgear to perform basic automatic transfer operations for a distribution switch installed in a primary selective or bus-tie system configuration. The control monitors two separate source voltages and their respective switch positions. When the source voltage is dead, the control automatically transfers electrical power to minimize the duration of power outages.

OPERATION


Primary-Selective System: The load(s) are combined on one solid bus and are all normally fed from a single source. The first source switch feeding the load(s) is normally closed and the second source switch (acting as the alternate, or backup source) is normally open. When the first source is lost, the control will open its switch and close the second switch, thereby restoring power to the load(s) from the alternate source.

Bus-Tie System: The loads are divided between the two sources and the bus is split with a normally open tie switch. The first source switch is normally closed and feeds load 1; while the second source switch is normally closed and feeds load 2. The loads are sized such that if either of the two sources are lost, the controller will open its switch and close in the bus tie switch; thereby feeding both loads from the one live source. ATC 201 only.

Emergency Return Function: If the preferred source is lost, the control transfers over to the alternate source. After some time, the preferred source returns and the control begins the return transfer delay timer (or waits for the time-of-day window setting). During this timing process, the alternate source is lost. Under this circumstance, the control will ignore the remainder of the return transfer delay timer and will immediately transfer back to the preferred source in an open transition mode (open the alternate source before closing the preferred source switch) - regardless of how the normal return or initial transfer operation sequence is set.

SETTINGS FEATURES


The control logic parameters are field selectable and determine the specific operation sequence, timing, and source preference for the auto transfer operations. The parameter selections are as follows:

System Configuration Selection: User selects between a Primary-Selective (Combined Load) and a Bus-Tie Configuration. ATC 201only.

Preferred Source Selection:
The choices for this setting are: SOURCE 1, SOURCE 2, or NONE. When a source is selected as "Preferred," the control will always try to serve the load from this source (as long as this source is healthy). If the preferred source is lost, the control will transfer to the alternate source (as long as that source is healthy). If the user selects NONE in this setting, the control will only perform initial transfers.

Operation Sequence Selection Initial and Return Transfers: The choices for these setting are: "OPEN before CLOSE" or "CLOSE before OPEN." The selection determines if the sources will be paralleled or not during an operation sequence.

Initial and Return Transfer: Delay Timers and Time-of-Day Window
The user selects a countdown timer setting to add a delay from the time the voltage is dead and the time the switch begins the transfer. In the ATC 201, the user selects between a countdown delay timer and a time-of-day window for the return transfer operation.

Paralleling of Sources Setting: The user will be able to select between Yes and No. A Yes setting will allow the control to have both source switches closed at the same time. If a No is selected, the user will not be able to close both switches at the same time.

Auto/Manual Mode Setting: If the user selects the Auto Mode, the automatic transfer logic is enabled. No manual electrical open or close operations are allowed, and the control will only respond to the automatic transfer logic. The Manual Mode disables the automatic transfer logic and (in combination with the Local setting) allows the user to use the local electronics to open and close the switches manually. In combination with the Remote Mode setting, the user is allowed to open and close the switches via remote SCADA.


Local/Remote Setting: If the user selects the Local Mode, all remote access is blocked from the unit. If the user selects the Remote Mode access to the control is allowed.

Test Mode Setting: While in the Test Mode, the user is able to simulate the loss and return of both sources, simulate a low dielectric condition, and simulate an overcurrent. If the motors can be decoupled, the test mode will also operate the motors to test the complete system, without actually operating the switches.

Overcurrent Lockout: If the overcurrent lockout input is activated, the control is blocked from performing any local, remote, or automatic operations. The overcurrent inputs will come from either a digital (ATC 101 and ATC 201) or analog source (ATC 201 only) that will activate when this device detects a downstream fault. The condition is reset locally at the control once the fault condition has been removed.

Low Dielectric Condition: This feature is applicable for SF6 switches only. If the low dielectric input is activated, the control is blocked from performing any local, remote, or automatic operations and will automatically reset itself once the low dielectric condition is removed.

Voltage Sensing: Three-phase voltage monitoring is required on both sources. This control will accept either digital (ATC 101 and ATC 201) or analog (ATC 201 only) voltage sensing for each source. If any one of the 3 phases is lost, the source will indicate dead. All 3 sources need to be live for a live source indication.

Generator Source Feature: The user will have the ability to set Source 1, Source 2, or NONE as a generator. In this case, when the preferred source is lost and the initial transfer delay timer has expired, the control will activate (close) the Generator Start Contact. The customer will connect this contact to their generator. Once the generator is up and running, its voltage sensors will activate as a good source. The control will then initiate the transfer from the utility source to the generator alternate source. Once the preferred source returns and the return transfer delay timer expires, the control will:

1. Initiate the return transfer to the preferred source; and

2. Begin the Generator Cool Down Timer.

When the timer expires, the control will activate the Generator Stop Contact.

Events Recorder: Each ATC 201 shall have an internal sequence of events recorder. The most recent events are logged with a time/date stamp. The sequence of events recorder is an option for the ATC 101.

USER-INTERFACE AND FRONT PANEL


For the ATC 101, all settings and operations of the control shall be viewed and adjusted without the use of a keypad/display or any other tools. The ATC 201 shall have a keypad/LCD interface. Both ATC controls shall provide system status, parameter settings, local manual operation, test mode operation, and SCADA outputs all integral in one control.

ENCLOSURE


The standard enclosure shall be padlockable and rated NEMA 4. NEMA 4X and 6P enclosures shall be available as options.

STANDARDS


The ATC package shall be rated for -30ºC to +65ºC. The control shall meet applicable sections of the following standards:
• ANSI/IEEE C37.90.2
• ANSI/IEEE C37.90.1
• IEC 60255-22-2
• IEC 60255-21-1 First Edition – 1998
• IEC 60255-21-2 First Edition – 1998

SCADA OUTPUTS


This control shall have a pre-wired terminal block for easy access and connection to an external RTU. The terminal block shall have all of the digital status points available from the control and control outputs so the user can remotely take control over the switch and operate the two switch mechanisms open or closed.

 
Site Map