G & W Electric
ISO 9001: 2000 and 14001 Certified
More Information
Literature
   
   
     

Typical Specifications
Oil Immersed Terminations - 69 to 245kV

General
This specification covers the requirements for a transmission voltage, extruded dielectic cable terminations for oil filled transformer or switchgear applications. The termination design shall be G&W style PATR and suitable for use on single conductor cables through 245 kV. The terminations shall be used on single copper or aluminum conductor cable with extruded insulation from 240-2500 mm2 (500 - 5000 kcmil).

Standards and Ratings

The terminations shall be designed, tested and built in accordance with applicable sections of IEC 840, IEEE 48 for Class 1 terminations, AEIC CS7 and AEIC CS6. The terminations shall be rated:

Rated Voltage, kV (IEC) 72.5 123 145 170 245
Rated Voltage, kV (IEEE) 69 115 138 161 230
Rated Voltage, kV (IEEE) 350 550 650 750 1050


Standard Components
Catalog number Includes:
• Epoxy insulator with built-in cable shield break
• Mechanical shrink stress cone
• Dielectric fluid
• Retained “O” ring seals on top and bottom
• Silver-plated copper or aluminum crimp-type connector
• Contact pad or stem connector style equipment interface
• Aluminum body
• Clamping ring
• Aluminum cable entrance and heat shrink cable jacket seal

Options
• Bi-metallic crimp-style or migweld bi-metallic connector with silver-plated copper top
• Wiping sleeve entrance.

 

 