For self-contained
cable systems per IEC 859 Standards.
Terminations and termination enclosures
for high voltage gas insulated switchgear (GIS) are required
in IEC 859 standards to meet specified dimension requirements
in order to be interchangeable. To accommodate this
requirement, G&W has modified its line of time proven
ATL style terminations to meet the dimensional requirements
specified in IEC 859 standards.
| Features: |
 |
Reliable
support insulator – High grade, non-tracking,
epoxy insulators provide excellent mechanical and electrical
characteristics. The insulators are compatible with
SF6 gas by-products, ensuring long life of the termination.
The design of the insulators also allows for an optional
cable shield break. |
 |
Field
proven stress control – Pre-perforated
paper rolls provide gradual stress relief and reduce
installation time of the termination. Perforations permit
applying the rolls of impregnated paper in a cylindrical
form on the cable and tearing the paper at perforations
to produce the required contour. The paper roll is computer
generated at the factory for the specific cable to provide
optimum stress control. |
 |
Rigid
cable support – The connector is locked
in position by a threaded hood at the top of the support
insulator. The electrical connection between the
GIS and termination is not subjected to the mechanical
forces from the cable. |
 |
Positive
sealing system – A double “O”
ring sealing system is used to seal between the termination
oil compartment and the GIS SF6 compartment. Fully retained
gaskets are compressed to seal the interior of the termination
from the atmosphere. |
 |
Ease
of installation – A kit consisting of a
temporary installation support for the paper roll and
necessary consumable material facilitate installation.
Installation time is significantly reduced using
perforated paper rolls; and the construction supervisor
can readily determine that all dimensions of cable preparation
are in accordance with specifications. |
 |
Fully
Tested - G&W ATL-A-SF terminations are designed
and tested in accordance with IEEE 48 for Class 1 terminations,
IEC 859 and IEC 141-1. |
Applications:
G&W’s ATL-A-SF style terminations are designed for
self contained liquid filled cables up to 4000 kcmil at 115kV
and 138kV and approximately 3200 kcmil at 161kV.
Electrical Ratings:
| Max. Voltage*
|
115
- 161 kV |
| BIL Impulse
|
550
- 750 kV |
| Continuous
Current |
Same
as cable |
| Cable Range |
250
- 4000 kcmil
(127 - 2000 mm2) |
*Corresponding ratings per IEC are 123kV,
145kV, and 170kV.
|