Source Switch Electrical Ratings:
Max. Voltage, kV
15.5
27
38
BIL Impulse, kV
110
125
150
One Minute Withstand, AC kV
35
60
70
15 Minute Withstand, DC kV
53
78
103
Continuous Current, A
630
630
630
Momentary Current, kA asym
40
40
40
Fault-Close Current, kA asym
40
40
40
One Second Current, kA sym
25
25
25
Open Gap Withstand, kV
200
200
200
10 Operation Overload Interrupting Capability, A
3000
3000
3000

Above tested to 1200 load break operations at full rated current and 2000 mechanical operations.

Vacuum Interrupter (VI) Electrical Ratings:
Max. Voltage, kV
15.5
27
38
BIL Impulse, kV
95
125
50
One Minute Withstand, AC kV
50
60
70
15 Minute Withstand, DC kV
53
78
103
Continuous, A
630
630
630
Interrupting, kA sym*
12
12
12

* 20kA sym. available

 

 