G & W Electric
ISO 9001: 2000 and 14001 Certified
More Information

Test Reports

  - 12.5kA ANSI

  - 12.5kA Arc

  - 25kA ANSI

  - 25kA Arc

Literature
Ratings
Accessories / Options
Overcurrent Controls
Specifications
 

- Padmount

- Vault

     

Vantage® SF6 Switchgear                                  

Rated through 38kV, 630A,

25kA sym. interrupting.

Provides both load break visible break and 25kA symmetrical interrupting.  Open/close switching with integral ground position simplifies system grounding procedures.  Large viewing windows help verify switch contact position for operating personnel.  Designs are available for both padmount and vault applications.

Tested to IEEE C37.74 and C37.60 standards.  Switches comply to arc resistance requirements of 25kA for 15 cycles per IEC 62271-201, Annex A.

Features:

38kV, 25kA sym. fault interruption and

fault making (12.5kA design available)

Low profile, small footprint

Large viewing window (6" x 8" rectangle)

Temperature compensated pressure gauge

Visual disconnect and ground capability

Hookstick or rope operable

Manual close/ open/ ground operation

with lockout handle for operator safety

Front / back access

630A continuous load ( 800A available)

Fully complies with IEEE C37.74 and C37.60

Arc resistance, 25kV for 15 cycles per

IEC62271-201, Annex A

 

 
 
 
Site Map