Load interrupting with 20kA asymmetrical
momentary and fault interrupting to 12kA symmetrical.
G&W Rotary Puffer Vacuum Interrupters
(RPFI) combine the total cost and operating benefits of fuseless,
electronically controlled, resettable overcurrent protection
with the safety and maintenance benefits of a totally sealed,
deadfront, SF6 insulated device. The switches are designed
for automatic single or three phase fault interruption with
manual load break capabilities for systems through 27kV, 630A
continuous.
| Features:
|
 |
Operator Safety
— G&W Rotary Puffer Vacuum Interrupters are
totally sealed, deadfront and insulated with nonflammable,
nontoxic SF6 gas. Operators are spring assisted for positive
quick-make, quick-break operation. A trip-free mechanism
permits interruption independent of the operating handle
if closing into a fault. Viewing windows permit visible
indication of interrupter contact position. Enclosures
provide tamper-resistant construction with penta-head
bolts and padlock provisions. |
 |
Minimal Maintenance
— No more routine inspections or dielectric testing
as with oil gear. No more contact contamination, rodent
problems or insulator maintenance as with air gear. A
periodic check of the gas pressure gauge is all that is
required. |
 |
Three
Phase Tripping — No more single phasing problems.
Simultaneous three phase tripping is available through
the electronics and with three phase operating handles
for manual operation and reset. |
 |
Protection
Curve Compatibility — No need to recoordinate
your distribution system. G&W solid state electronic
controls permit extremely accurate, consistent protection
curve characteristics compared to conventional fuses.
The exclusive controls can emulate the most common time
current curves (TCC) for power fuses, relays and fuse
links (oil fuse cutouts). Optional electronic packages
can provide ground trip, inrush restraint and adjustable
time delay capability. |
 |
User
Friendly Controls — Specific TCC characteristics
are easily field selectable. Controls permit individual
phase trip setting selection from twelve available levels. |
Applications:
G&W RPFIs provide a direct
replacement for power fused air and vacuum-in-oil switchgear.
Some ideal applications include:
 |
Transformer
and Motor Protection — The three phase trip
feature and high continuous current capability make RPFIs
ideal for protecting three phase motors and transformers. |
 |
Loop and Tap
Switching — Full 630A loop switching is accomplished
using the latest puffer technology. Tap switching through
630A and 12 to 18kA symmetric fault protection is accomplished
using resettable, electronically controlled vacuum interrupters.
The vacuum interrupters can also function as load break
switches. |
 |
Automatic
Transfer — For critical load applications,
RPFIs can be supplied with an automatic transfer control
package to provide automatic transfer from one feeder
to another to minimize downtime. |
 |
Remote/SCADA
Control — G&W RPFIs can be supplied with
motor actuators on both the line and load side providing
remote control capability. Various control packages including
portable DC controllers for onsite operation or complete
SCADA /RTU systems are available. |
 |
Metalclad
Switchgear Replacement — Front access RPFI
designs provide switching alongside multiple vacuum interrupter
protected tap ways for an extremely compact, economical
alternative to metalclad or metal enclosed lineups. |
|