Two Position Rotary Puffer (RP) Ratings

Electrical Ratings:
Max. Voltage, kV
15.5
27
BIL Impulse, kV
110
125
One Minute Withstand, AC kV
35
60
15 Minute Withstand, DC kV
53
78
Continuous Current, A
630
630
Momentary Current, kA asym
25
20
Fault-Close Current, kA asym
25
20
One Second Current, kA sym
16
12.5

Above tested to 500 load break operations at full rated current at 15kV (350 @ 25kV) and 2000 mechanical operations.

 

 