The switch shall consist of manually operated
load interrupting, SF6 insulated, 600A rotary puffer switches.
The switch manufacturer shall be ISO
9001:2000 and 14001 certified.
A. SWITCH CONFIGURATION
Switches shall be designed for front access to cables and
operators. Entrance bushings shall be arranged:
_____ diagonally (SPRAM-RP style) or
_____ in-line (PRAM-RP style).
Each switch shall have:
_____ (Qty.) 3-phase load switched ways
_____ (Qty.) 3-phase load unswitched ways
B. SWITCH CONSTRUCTION
All switch components and entrances shall be assembled in
a totally welded mild steel tank. Entrances shall be internally
connected by copper conductors capable of handling momentary
and continuous current duty. The switch shall contain no electrically
floating metallic parts or components. Construction shall
be a deadfront design. Switch tanks shall be painted ASA70
light gray using a corrosion-resistant epoxy paint.
Each switching way is to be equipped with
an internally mounted operating mechanism capable of providing
quick-make, quick-break operation in either switching direction.
The mechanism must be capable of delivering sufficient torque
and shall be provided with latches for each position to assure
load interrupting, fault closing and momentary ratings. All
switch positions are to be clearly identified, padlockable
and adaptable to keylock schemes. The operating mechanism
shall be actuated from outside the switch tank with an operating
handle. The operating shaft shall be made of stainless providing
maximum corrosion resistance. A double "O" ring
type operating shaft seal shall be used for a leak resistant,
long life seal.
Switch contacts shall be of a rotary puffer
design made with copper alloy contacts with silver plating
to assure permanent, low contact resistance. Each rotating
contact simultaneously disengages from two fixed contacts,
thus providing two break points per phase giving improved
interrupt capability compared to single break contact systems.
Contact travel shall be 90 degrees to assure efficient arc
extinction and a wide open contact gap. Arcing is confined
away from the main contact surfaces. The stationary contacts
shall be supported independent of the cable entrance bushings,
eliminating possible misalignment. Auxiliary blades used for
load interruption are not acceptable.
C. DESIGN RATINGS
AND STANDARDS
Switches shall be designed, tested and built per ANSI C37.72-1987
and IEC 265 standards. Certified test reports shall be provided.
The switch shall be rated: (select column)
| Maximum design
voltage kV |
15.5 |
27 |
| Impulse level
(BIL), kV |
110 |
125 |
| Continuous
& load break current, A |
630 |
630 |
| One minute
withstand (dry), AC kV |
35 |
60 |
| One minute
withstand (dry), AC kV Production test rating |
34 |
40 |
| 15 minute
withstand, DC kV |
53 |
78 |
| Momentary
current, kA, ASYM |
20 |
20 |
| Fault-close
current, kA, ASYM |
20 |
20 |
| One second
current, kA, SYM |
12 |
12 |
Load break
operations
at 600 A |
500 |
500 |
| Mechanical
endurance, operations |
2000 |
2000 |
D. CABLE ENTRANCES
Cable entrances shall be tested to ANSI/IEEE 386 and be one
or more of the following: (check)
____ 600 amp Quik-Change disconnectable
apparatus bushing
____ 600 amp Apparatus bushing
____ 600 amp Universal bushing
E. ENCLOSURE
Enclosures shall be made of 12 gauge mild steel and manufactured
to ANSI C37.72 and C57.12.28 standards. The enclosure shall
be mounted independent of the switch allowing removal for
ease of cable installation or future replacement if required.
Enclosures shall be tamper-resistant incorporating hinged
access doors with pentahead locking bolts and provisions for
padlocking. The enclosure shall be provided with lifting provisions
and painted with a Munsell 7.0GY3.29/1.5 green finish.
F. FACTORY PRODUCTION
TESTS
The bulk SF6 gas supply and each individual switch shall be
tested for moisture content. Each individual switch shall
undergo a mechanical operation check and a leak test. The
switch shall be factory filled with SF6 and AC hi-pot tested
one minute phase-to-phase, phase-to-ground and across the
open contacts. Circuit resistance shall be checked on all
ways.
Switches will be shipped factory filled
with SF6 gas. Tank shall be designed to withstand 15 psig
internal pressure and an external pressure of 14 psig without
affecting the performance of the switch.
G. STANDARD COMPONENTS
The following shall be included as standard:
- Welded steel tank painted light gray with
stainless steel and brass fasteners.
- Lifting provisions.
- Gas pressure gauge and fill valve.
- Grounding provisions for switch tank and
all cable entrances.
- Stainless steel three line diagram and
corrosion-resistant nameplates.
- Parking stands.
- Switch operating handle(s) with padlock
provision and end stops.
- 12 gauge mild steel padmount enclosure
painted Munsell green with stainless steel hinges and pentahead
locking mechanisms.
H. OPTIONAL COMPONENTS
(check)
The following options shall be supplied:
___ Stainless steel tank.
___ Stainless steel enclosure.
___ Low pressure warning device.
___ SF6 density switch for SCADA or remote
indication of dielectric.
___ 4/0 brass ground lug(s).
___ Keylock provisions.
___ Current transformers (500:1) (1000:1)
___ Automatic transfer control package for
a maximum 5 seconds per mechanical switching operation.
___ 24VDC Motor actuators.
___ Switch controllers.
___ Remote Terminal Units.
___ Auxiliary contacts.
___ Analog voltage sensors.
___ Digital voltage sensors.
___ Refill kit consisting of regulator,
hose and 10 or 20 lb SF6 bottle.
|