VIPER-S® Solid Dielectric, Three Phase Recloser Ratings

Electrical Ratings:
Maximum Design Voltage, kV 
15.5
27
38
Impulse level (BIL), kV
110
125
150
Continuous & load break current, A
800
800
800
8-hour Overload, A rms
960
960
960
60Hz Withstand, kV rms
  One minute (dry)
  10 second (wet)

50
45

60
50

70
60
Radio Influence Voltage, microvolts 100 @
9.4kV
16.4kV
23kV
Interrupting Current, kA rms sym.
12.5
12.5
12.5
Making Current, kA asym. rms
20
20
20
Making Current, kA asym. peak
32
32
32
Short Circuit Current, kA sym., 3 second
12.5
12.5
12.5
Mechanical endurance, operations
10,000
10,000
10,000

 

 