Fault
interrupting to 50kA symmetrical.
For applications through 23kV requiring current limitation
and overcurrent interruption through 50kA
symmetrical,
SF6 switches can be equipped with integral air insulated,
canister style current limiting fusing.
G&W's
circular tank rotary puffer (RP) switch incorporates all bushings
and operating apparatus on the top of the switch. Switches
are rated through 23kV, 200A maximum continuous current.
Protected ways are rated per Table 3 (see bottom of page).
Two way and three way configurations are available for either
single, two or three phase applications. Single and
parallel fuse holders are available.
| Features:
|

Mechanical
interlock prevents fuse access if switch is in the closed
position. |
 |
Compact, dead-front construction. |
 |
Mechanical
or key interlocking arrangements preventing access to
the fuses unless the switch is in the open position. |
 |
Safe,
quick fuse replacement using conventional tools and
without exposing switch dielectric or current carrying
parts to environmental contamination. |
 |
Two
fuses can be connected in parallel to double the capacity
rating of the switch. |
 |
Fuse
curves are available through your G&W representative. |

Table
1 - Single Fuse Holders
| One-Line
Diagram |
Voltage Class (kV) |
No. of Phases |
No. of Fuses |
Catalog Number* |
Approx. Dimensions Inches
(mm) |
Approx. Wt. w/
SF6 lbs. (kg) |
| A |
B |
 |
4.3,
5.5,
or 8.3 |
1 |
1 |
8FRPR1W |
29 (737) |
31 (787) |
160 (73) |
| 2 |
2 |
8FRPR2W |
29 (737) |
31 (787) |
170 (77) |
| 3 |
3 |
8FRPR3W |
29 (737) |
31 (787) |
180 (82) |
| 15 |
1 |
1 |
15FRPR1W |
29 (737) |
31 (787) |
160 (73) |
| 2 |
2 |
15FRPR2W |
29 (737) |
31 (787) |
170 (77) |
| 3 |
3 |
15FRPR3W |
29 (737) |
31 (787) |
180 (82) |
| 23 |
1 |
1 |
23FRPR1W |
29 (737) |
33 (838) |
160 (73) |
| 2 |
2 |
23FRPR2W |
29 (737) |
33 (838) |
170 (77) |
| 3 |
3 |
23FRPR3W |
29 (737) |
33 (838) |
180 (82) |
 |
4.3,
5.5,
or 8.3 |
1 |
1 |
8FRPRL1W |
35 (889) |
31 (787) |
200 (91) |
| 2 |
2 |
8FRPRL2W |
35 (889) |
31 (787) |
210 (95) |
| 3 |
3 |
8FRPRL3W |
35 (889) |
31 (787) |
220 (100) |
| 15 |
1 |
1 |
15FRPRL1W |
35 (889) |
31 (787) |
200 (91) |
| 2 |
2 |
15FRPRL2W |
35 (889) |
31 (787) |
210 (95) |
| 3 |
3 |
15FRPRL3W |
35 (889) |
31 (787) |
220 (100) |
| 23 |
1 |
1 |
23FRPRL1W |
35 (889) |
33 (838) |
200 (91) |
| 2 |
2 |
23FRPRL2W |
35 (889) |
33 (838) |
210 (95) |
| 3 |
3 |
23FRPRL3W |
35 (889) |
33 (838) |
220 (100) |
*
Suffix "W" denotes 200A deepwell bushings.
Replace "W" with "D" for 200A deadbreak
bushings or deepwell bushings with deadbreak inserts, "Q"
for 600A Quik-Change bushings, or "A" for 600A apparatus
bushings.
Table
2 - Parallel Fuse Holders
| One-Line Diagram |
Voltage Class (kV) |
No.
of Phases |
No. of Fuses |
Catalog Number* |
Approx. Dimensions Inches (mm)
|
Approx. Wt. w/ SF6
lbs. (kg) |
| A |
B |
 |
4.3,
5.5,
or 8.3 |
1 |
2 |
8FFRPR1W |
35 (889) |
31 (787) |
200 (91) |
| 2 |
4 |
8FFRPR2W |
35 (889) |
31 (787) |
210 (95) |
| 3 |
6 |
8FFRPR3W |
35 (889) |
31 (787) |
220 (100) |
| 15 |
1 |
2 |
15FFRPR1W |
35 (889) |
31 (787) |
200 (91) |
| 2 |
4 |
15FFRPR2W |
35 (889) |
31 (787) |
210 (95) |
| 3 |
6 |
15FFRPR3W |
35 (889) |
31 (787) |
220 (100) |
| 23 |
1 |
2 |
23FFRPR1W |
35 (889) |
33 (838) |
200 (91) |
| 2 |
4 |
23FFRPR2W |
35 (889) |
33 (838) |
210 (95) |
| 3 |
6 |
23FFRPR3W |
35 (889) |
33 (838) |
220 (100) |
*
Suffix "W" denotes 200A deepwell bushings.
Replace "W" with "D" for 200A deadbreak
bushings or deepwell bushings with deadbreak inserts,
"Q" for 600A Quik-Change bushings, or "A"
for 600A apparatus bushings.
| Typical
Specifications |
| Add
the following information to the appropriate fused switch
specifications. |
| Canister
Fusing Construction |
|
Fusing
shall be deadfront and submersible using non-venting,
current limiting fuses installed in drywell canisters
built into the switch. The fuses shall be ANSI
C37.473.C rated, interrupting both high and low level
fault currents while limiting the available fault current
on the system.
The
fuseholder shall be located for easy fuse replacement
and be interlocked to prevent fuse removal unless the
series switch is open. |

Standard
hook stick fuse removal and replacement. |
| Standard
Components |
 |
Replaceable and interchangable,
commercially available, general purpose current limiting
fuses. |
 |
Provisions for standard hook stick
fuse removal and replacement. |
 |
Single or parallel fuseholders as specified. |
Table
3 - Air Canister Style Fuse Ratings
| Types of Fuseholders
by Voltage Class |
Single Holder Fuse Ratings |
Parallel Holder Fuse Ratings |
| 8.3kV
Max.
95kV BIL |
18
to 82 Amp at 4.3kV Max. |
90 to 164
Amp at 4.3kV Max. |
| 6 to 72 Amp at 5.5kV Max. |
80 to 144
Amp at 5.5kV Max. |
| 1.5 to 40 Amp at 8.3kV Max. |
50 to 80 Amp at 8.3kV Max. |
| 15.5kV
Max.
125kV BIL
|
1.5 to 40
Amp at 15.5kV Max. |
34 to 80 Amp* at 15.5kV Max. |
| 23kV
Max.
125kV BIL
|
6 to 29 Amp at 23kV Max. |
30 to 58 Amp* at 23kV Max. |
*
Fuses rated above 25 Amps are required to be nongassing fuses.
|