Switches combine rotary puffer style load break switching with electronically controlled, vacuum interrupter overcurrent protection in a deadfront, submersible device. Front and back compartments include source and tap side cables on one side and all switch operators on the other.
Load break switch (RP) ratings
Maximum design voltage
15.5 kV
27 kV
38 kV
Voltage class
15 kV
25 kV
35 kV
Impulse level (BIL)
110 kV
125 kV
150 kV
One minute withstand
35 AC kV
60 AC kV
70 kV
One minute withstand, production test rating
34 AC kV
40 AC kV
50 kV
15 minute withstand
53 DC kV
78 DC kV
103 kV
Continuous and load break current
630 Amps
Momentary current
40 kA asym
Fault close current, (3 times)
32 kA asym
One second current
25 kA sym
Mechanical endurance, operations
2000
Fault Interrupter (NI) ratings
50 AC kV
70 AC kV
One minute withstand, Production test rating
103 DC kV
Symmetrical interrupting rating
12.5 kA
IEEE C37.60
Fault Interrupting Duty
Total number of fault interruptions: 116
Percent of Maximum Interrupting Rating
Approx. Interrupting Current, Amps
No. of Fault Interruptions
15 – 20%
5,000
44
45 – 55%
12,500
56
90 – 100%
25,000
16