The Vantage provides visible break on both load break and fault interrupting ways. The switch can be ordered with 12.5kA or 25kA symmetrical interrupting. Open / close switching with integral ground position simplifies system grounding procedures. Large viewing windows help verify switch contact position for operating personnel.
Load break switch ratings
Maximum design voltage
15.5 kV
27 kV
38 kV
Impulse level (BIL)
110 kV
125 kV
150 kV
Continuous and load break current
630 Amps
One minute withstand, (dry)
35 AC kV
60 AC kV
70 kV
One minute withstand, (dry) Production test rating
34 AC kV
40 AC kV
50 kV
15 minute withstand
53 DC kV
78 DC kV
103 kV
Momentary current
40 kA asym
Fault close current, (3 times)
One second current
25 kA sym
Mechanical endurance, operations
2000
Fault Interrupter ratings
50 AC kV
70 AC kV
Symmetrical interrupting rating
25 kA
Asym. Interrupting rating
IEEE C37.60 Fault Interrupting Duty Total number of fault interruptions: 116
Percent of Maximum Interrupting Rating
Approx. Interrupting Current, Amps
No. of Fault Interruptions
15 – 20%
5,000
44
45 – 55%
12,500
56
90 – 100%
25,000
16